TD90_IP20_60530_1
2023-12-22
- The priority of error codes has been updated, resolving the bug where the host error persisted while the subordinate continued to operate.
- The bug preventing shutdown in sleep mode has been fixed.
TD90_IP20_60528_1
2023-11-10
- Restored relay functionality, function code 31.
F06.62 = Lower limit of sensor signal
F06.63 = Upper limit of sensor signal
TD90_IP20_60527_1
2023-11-09
- Add F06.61 pipeline fill status (read-only, 0 for idle, 1 for in operation).
TD90_IP65_60331_1
2023-10-18
- Testing functionality completed; added display of fill status.
Pipeline filling frequency: F06.58
Pipeline filling time: F06.59
Pipeline filling target pressure (should be lower than the target pressure): F06.60
Pipeline filling status (read-only, 0 for standby, 1 for in progress): F06.61
IP20_60525_1
2023-09-11
- Resolve the issue of conflict between the negative feature of F10.03 and the sleep mode.
IP65_60328_1
2023-09-07
- Resolve the issue of conflict between the negative feature of F10.03 and the sleep mode.
IP20_60524_test2
2023-09-07
- Addition: Pipeline filling feature
Parameter F06.58: Pipeline filling frequency
Parameter F06.59: Pipeline filling time
Parameter F06.60: Pipeline filling target pressure
- Adjustment: Modify the sleep condition attainment threshold from 90% to 98%.
IP20_60523_1、IP65_60327_1
2023-04-04
- If three or more units are offline, including both the primary and secondary units, the standby unit will still be able to go online. In previous versions, the standby unit would not automatically go online.
IP20_60522_3、IP65_60326_1
2023-02-02
F05.65 represents the time for setting a timed malfunction.
F05.66 represents the unit setting, where setting it to 1 corresponds to seconds (s), and setting it to 0 corresponds to hours.
F05.67 represents the automatic reset time for E070 faults, measured in seconds (s).
F05.68 represents the automatic reset time for E030 faults, also measured in seconds (s).
IP20_60522_1
2023-01-30
- Adjustment: The maximum value supported for parameter F05.20 is 6000.0 seconds.
- Addition: Parameter F05.65 introduces a timed fault E070, where the most significant bit represents the unit of measurement. If the most significant bit is 0, the unit is hours; if it is 1, the unit is seconds. The maximum supported value is 2000 hours or 2000 seconds.
- Parameter F05.66 sets the automatic reset time for fault E070, with the current upper limit set at 100 seconds.
Fault F05.67 has a preset recovery time of E030, which is currently set to a default value of 36000 seconds. However, there is a bug in the system causing the frequency converter to fail to start after the fault is recovered, and manual mode is also unable to initiate.
IP20_60521_1
2023-01-13
The functionality of fault code F05.64 has been disabled due to error code E060.
P20_60520_1
2023-01-11
- Rectify the bug that prevents the device from entering sleep mode when the wake-up delay time F09.51 is not set to 0.
IP65_60324_2
2022-12-29
F17.73 is synchronized with the standby indicator light.
2023-01-01 BUG
The default value for the wake-up delay time F09.51 upon factory settings is 0.0. If it is modified to any other numerical value, the device will be unable to wake up after entering sleep mode.
IP65_60324_1
2022-12-25
- 与IP20_60519软件同步更新,暂未将F17.73与standby指示灯同步
IP20_60519_2
2022-12-14
- We have not yet synchronized the F17.73 with the standby indicator light, as per the IP20_60519 software update.
IP20_60517_3
2022-12-09
- Modify parameter F17.73 to synchronize with the status of the standby indicator light.
IP20_60517_2
2022-12-07
- Change the feedback pressure in manual mode to real-time updating.
IP20_60517_1、IP_65_60323_1
2022-12-06
- Bug fix: After entering sleep mode, one of the slave machines fails to start when switching to manual mode.
IP65_60317
2022-07-08
- I have primarily added F05.62, the shutdown handling mode; 0: remains the same as before, 1: avoids communication congestion, 2: multiple shutdown commands.
Number of shutdown command transmissions (valid when F05.62=2).
IP20_60513-2、IP65_60322_1
2022-10-18
- Rectify the machinery function: After entering sleep mode, the machinery will be restarted. The time-based machinery has been enhanced to execute in seconds. When selecting seconds, it is possible to configure F00.28=2 to clear any portion that is less than one hour.
- Enable frequency setting for the offload detection function. Parameter F06.57 sets the frequency limitation (F05.12 sets the function switch, F05.13 sets the detection current percentage, and F05.14 sets the detection time).
IP65_60315、TD90_IP20_60504
2022-04-27
F05.61: Set the maximum number of activated water pumps in automatic mode.
F26.07: Modify the priority for starting inverters with lower stack numbers to 0, inverters with shorter running times to 1, and sequentially rotate based on Modbus addresses to 2.
F26.29: When set to 2, it is possible to configure the manual or automatic mode through the upper-level computer (communication address 2005H, where data 0 represents automatic mode, 1 represents manual mode, with power loss memory).
- Send external fault command with data 9 to communication address 1000H, resulting in the variable frequency drive (VFD) entering a free stop state (sending this command to the host will stop the main pump, auxiliary pump, and secondary pump).
IP20_60503
2022-03-23
F05.61: Set the maximum number of activated water pumps in automatic mode.
F26.07: Modify the priority for starting inverters with lower stack numbers to 0, inverters with shorter running times to 1, and sequentially rotate based on Modbus addresses to 2.
F26.29: When set to 2, it is possible to configure the manual or automatic mode through the upper-level computer (communication address 2005H, where data 0 represents automatic mode, 1 represents manual mode, with power loss memory).
- Send external fault command with data 9 to communication address 1000H, resulting in the variable frequency drive (VFD) entering a free stop state (sending this command to the host will stop the main pump, auxiliary pump, and secondary pump).
PS:
There are a few issues with this version, which have been updated in later versions
IP20_60501
- This version lacks an automatic external fault reset feature, which would enable the automatic switching of the host when there is a terminal input external fault causing a shutdown.